Phoenix-E - Item # Model 12
Phoenix-E - Creating Better Workplaces Worldwide
Home | Online Catalog | About Us | Literature | RFQ | Contact Us
Call Us Today: 800.241.4207, E-mail: info@phoenix-e.com
  Noise Control
Solutions
Controlled and Critical Environments Functional Buildings, Enclosures, Mezzanines and Vertical Conveyors H-Occupancies / Hazardous EnvironmentsAcoustical Test FacilitiesLiterature

All Categories > Noise Control Solutions > SonoCon Sound Control Materials > Overhead Acoustical Baffle Systems > Vinyl & Fabric Faced Baffles > SonoCon Models 4, 6, 6R, 8, 12, 6S > Item # Model 12  
    Print Printable Page     Email Email This Page     Save To Favorites Save To Favorites
Request Information

Item # Model 12



    Email Email This Page  
    Save To Favorites Save To Favorites
  


SonoCon acoustical louvers are fabricated in various assembly depths to match the sound attenuation requirements. These are typically installed in the building walls to reduce the noise transmitted through the ventilation openings needed for mechanical equipment cooling or air distribution. SonoCon louvers are easily installed in panelized or conventional construction and require little additional floor area.

Requirements for aesthetic design, corrosion resistance, pressure drop and insertion loss dictate the design of the acoustical louvers. Generally, acoustical louvers are either aluminum or galvanized steel with airfoil or parallel surfaces.

Grilled, weather-resistant and storm-proof styles are available. Each is rated by independent laboratory testing for both sound attenuation and aerodynamic performance. Pressure drop as a function of face velocity is provided in the performance tables to assist in quickly sizing the acoustical louver area needed to meet ventilation requirements.
    In addition to standard constructions the following options can be furnished :
  • Aluminum, stainless steel and heavier gauge galvanized steels.
  • Aluminum constructions can be anodized in any of the following : Clear #204-R1 or #215-R1 Bronze: Light, medium, dark or black.
  • Flanged frames. 2” flange standard. Other sizes available.
  • Galvanized screen : 1/2” x 1/2” x 19 gage is standard. Other sizes and materials can be supplied, including various expanded metal configurations.
  • Thermal setting powder coating and Kynar finishes.
  • Louvered doors with passage or locking hardware.



Specifications · Performance · Aerodynamic Performance

Specifications

Frame

16 Gauge Galvanized Steel Channel

Blades

16 Gauge Galvanized Steel

Blade Spacing

6 in
9 in

Finish

Mill Finish

Min. Size

24 x 24 in

Max. Size

72 x 96 in

Depth

12 in


Performance
Acoustic Performance
Octave Band 1 2 3 4 5 6 7     8    
Ctr. Frq. Hz 63 125 250 500 1K 2K 4K 8K
TL. dB 6" 5 7 9 11 16 18 12 10
TL. dB 9" 3 6 7 9 14 13 11 10
NR. dB 6" 11 13 15 17 22 24 20 15
NR. dB 9" 9 12 14 17 20 18 17 15





Aerodynamic Performance
Aerodynamic Performance
Press. Loss, in.     .05 .15 .20 .35 .45 .60 .75   1.0  
Face Velocity, FPM 6" 200 346 385 517 571 675 750 829
Face Velocity, FPM 9" 250 429 500 650 746 850 965 1122




 MORE IMAGES 

· SonoCon Typical Acoustical Louver Applications

· Sono-Con Model 12


 DOWNLOADS 

 width= SonoCon-Louver-Brochure
(PDF, 1048KB)


Request Information
 

 
GO

Applications

• Cogeneration
• Power Plants
• Water Treatment Plants
• Gas Utilities
• Cooling Towers
• Anechoic Rooms
• Control Rooms
• Explosion Proof Facilties

Literature

SONO-CON Literature
• Understanding Noise
   Control
• Noise Control
   Manufacturing - Power    Generation - Processing
• SonoCon HP Sound
   Absorption