SonoCon acoustical louvers are fabricated in various assembly depths to match the sound attenuation requirements. These are typically installed in the building walls to reduce the noise transmitted through the ventilation openings needed for mechanical equipment cooling or air distribution. SonoCon louvers are easily installed in panelized or conventional construction and require little additional floor area.
Requirements for aesthetic design, corrosion resistance, pressure drop and insertion loss dictate the design of the acoustical louvers. Generally, acoustical louvers are either aluminum or galvanized steel with airfoil or parallel surfaces.
Grilled, weather-resistant and storm-proof styles are available. Each is rated by independent laboratory testing for both sound attenuation and aerodynamic performance. Pressure drop as a function of face velocity is provided in the performance tables to assist in quickly sizing the acoustical louver area needed to meet ventilation requirements.
In addition to standard constructions the following options can be furnished :
Aluminum, stainless steel and heavier gauge galvanized steels.
Aluminum constructions can be anodized in any of the following : Clear #204-R1 or #215-R1 Bronze: Light, medium, dark or black.
Flanged frames. 2” flange standard. Other sizes available.
Galvanized screen : 1/2” x 1/2” x 19 gage is standard. Other sizes and materials can be supplied, including various expanded metal configurations.
Thermal setting powder coating and Kynar finishes.
Louvered doors with passage or locking hardware.
Specifications
·
Performance
Specifications
Frame
16 Gauge Galvanized Steel Channel
Blades
16 Gauge Galvanized Steel
Blade Spacing
5 in
Finish
Mill Finish
Min. Size
24 x 24 in
Max. Size
72 x 96 in
Depth
6 in
Performance
Acoustic Performance
Octave Band
1
2
3
4
5
6
7
    8    
Ctr. Frq. Hz
63
125
250
500
1K
2K
4K
8K
TL. dB
6
9
10
11
15
19
17
16
NR. dB
11
10
10
11
14
18
21
20
Aerodynamic Performance
Press. Loss, in.
.05
.15
.20
.35
.45
.60
.75
  1.0  
Face Velocity, FPM
185
205
237
313
355
410
458
529
MORE IMAGES
·
SonoCon Typical Acoustical Louver Applications
·
Sono-Con Model 6R
DOWNLOADS
SonoCon-Louver-Brochure
(PDF, 1048KB)
By Part Number
By Keyword
• Cogeneration
• Power Plants
• Water Treatment Plants
• Gas Utilities
• Cooling Towers
• Anechoic Rooms
• Control Rooms
• Explosion Proof Facilties
more...
• Understanding Noise
Control
• Noise Control
Manufacturing - Power Generation - Processing
• SonoCon HP Sound
Absorption
more...
339 Mobil Ave. • Camarillo, CA 93010 • Phone: 800.241.4207 • Fax: 805.987.2495
Sitemap
|
Privacy Policy